AISIKAI MCCB Normal working conditions and installation methods |
|
Category | Requirements |
Elevation | Installation site not exceeding 2000 meters above sea level |
Ambient air temperature | The upper limit does not exceed+ 40 ºC; the lower limit does not exceed - 5 ºC; the average value of 24 hours does not exceed + 35 ºC |
Pollution Level | Level 3 |
Installation Category | Installation Category III, Circuit Breaker 1600A IV |
Atmospheric conditions |
Atmospheric relative humidity does not exceed 50% when the ambient air temperature is + 40 C. It can have a higher relative humidity at a lower temperature. The average maximum relative humidity of the wettest month is 90%, and the average minimum temperature of the month is + 25 C. Considering the condensation occurring on the surface of the product due to temperature changes. |
Installation Conditions |
Installed in places without significant shaking and shock vibration, the magnetic field near the installation site should not exceed 5 limes of the magnetic field in any direction, and leakage circuit breakers should generally be installed vertically. |
Installation | Circuit breaker can be installed vertically (i.e. vertically) or horizontally (i.e. horizontally). |
Input mode | Circuit breaker can't go down, that is, only 1,3,5 power lines, 2,4,6 load lines |
AISIKAI Molded Case Circuil Breaker Main Technical Indicators | ||||||||
The setting value of instantaneous action characteristic of MCCB for distribution is 1O.ln±20%,ASKM-1600:7ln±20%, Setting value of instantaneous action characteristic of motor protection circuit breaker is 12±20%. | ||||||||
Item | Number of Pole | Rated current (A) | Rated Operating Voltage (V) | Rated insulation voltage (V) | Icu(Rated limit short-circuit breaking capacity) | Arcing distance (mm) |
||
Test voltage (V) | Icu (kA) | Ics(kA) | ||||||
ASKM1-63L | 3/4 | 10/16/20/25 /32/40/50/63 |
400 | 800 | 400*1.10 | 22 | 18 | 0 |
ASKM1-63M | 3/4 | 35 | 22 | |||||
ASKM1-125L | 3/4 | 16/20/25/32 /40/50/63/80 /100/125 |
400 | 800 | 400*1.10 | 35 | 22 | ≤50 |
ASKM1-125M | 3/4 | 50 | 35 | |||||
ASKM1-125H | 3/4 | 85 | 50 | |||||
ASKM1-125L | 3/4 | 690 | 10 | 5 | ||||
ASKM1-125M | 3/4 | 20 | 10 | |||||
ASKM1-250L | 3/4 | 100/125/140 /160/180/ 200/225/250 |
400 | 800 | 400*1.10 | 35 | 22 | |
ASKM1-250M | 3/4 | 50 | 35 | |||||
ASKM1-250H | 3/4 | 85 | 50 | |||||
ASKM1-250L | 3/4 | 690 | 10 | 5 | ||||
ASKM1-250M | 3/4 | 20 | 10 | |||||
ASKM1-400L | 3/4 | 225/250/315 /350/400 |
400 | 800 | 400*1.10 | 65 | 50 | ≤100 |
ASKM1-400M | 3/4 | |||||||
ASKM1-400H | 3/4 | |||||||
ASKM1-400L | 3/4 | 690 | ||||||
ASKM1-400M | 3/4 | |||||||
ASKM1-630L | 3/4 | 400/500/630 | 400 | 800 | 400*1.10 | 75 | 65 | |
ASKM1-630M | 3/4 | |||||||
ASKM1-630H | 3/4 | |||||||
ASKM1-630L | 3/4 | 690 | ||||||
ASKM1-630M | 3/4 | |||||||
ASKM1-800L | 3/4 | 630/700/800 | 400 | 800 | 400*1.10 | 85 | 70 | |
ASKM1-800M | 3/4 | |||||||
ASKM1-800H | 3/4 | |||||||
ASKM1-800M | 3/4 | 690 | ||||||
ASKM1-1600M | 3/4 | 800/1000 /1250/1600 |
400 | 800 | 400*1.10 | 85 | 65 | |
ASKM1-1600H | 3/4 | |||||||
ASKM1-1600M | 3/4 | 690 |