ltems | Requirements |
Operating temperature | -20 to 40'C. The average value for 24 hours shall not exceed +35°C; |
Operating humidity | The average humidity at +40℃ shall not exceed 50%. Higher relative humidity is allowed at lower temperatures, for example, up to 90% at+25℃. Special measures should be taken for occasional condensation due to temperature changes; |
Altitude | Lower than 2000 meters and, if higher than 2000 meters, please use at reduced ratings; |
Vibration and gas | There shall be no strong vibration or shock and no harmful gases to corrode the metals and to damage the insulation within the environment of its use; |
Surrounding material | There shall be no serious dust, conductive particles or explosive hazardous substances; |
Pollution level | Level 3 according to GB/T14048.11 |
Class of installation | Class IV accordingtoGB/T14048.11 |
Installation inclination | The product is fixedly installed in the cabinet, the maximum inclination is+22.5; |
Arcing distance | AC380V, arcing distance is 80mm; flash over 660v, arcing distance is100mm. |
Frame | 160F | 250F | 400F | 630F | ||||
Rated current le(A) | 63,80,100,125,140,150,160 | 160,180,200,225,250 | 250,315,350,400 | 400,500,630 | ||||
Standards complied | IEC69047-6-1 | |||||||
Rated frequency (Hz) | 50/60 | 50/60 | 50/60 | 50/60 | ||||
Poles (P) | 2 | 3,4 | 2 | 3,4 | 2 | 3,4 | 2 | 3,4 |
Rated operating voltage Ue(v)AC | 230 | 400 | 230 | 400 | 230 | 400 | 230 | 400 |
Control voltage (V) AC | 230 | |||||||
Rated insulation voltage Ui(v)AC | 1000 (main circuit); 500V (auxiliary circuit, control circuit) | |||||||
Rated impulse withstand voltage Uimp(kV) | 8 | 8 | 8 | 8 | ||||
Rated conditional short-circuit current lq (fuse protection) (kA) | 100 | 100 | 100 | 100 | ||||
Rated conditional short-circuit current lq (Circuit breaker protection) (kA) | 50 | 50 | 50 | 50 | ||||
Rated short-time withstand current lcw(kA/s) | 10kA/60ms | 10kA/60ms | 10kA/60ms | 10kA/60ms | ||||
Rated short-circuit making capacity lcm(kA) | 17 | 17 | 34 | 34 | ||||
Category of use | AC-33A | AC-33A | AC-33A | AC-33A | ||||
Mechanical life (times) | 10000 | 10000 | 10000 | 10000 | ||||
Electrical life (times) | 6000 | 6000 | 6000 | 6000 | ||||
Number of operating cycles (times/h) | 120 | 120 | 120 | 120 | ||||
Contact switching time (ms)≤ | 70 (Type J) / 200 (Type X) | 70 (Type J) / 200 (Type X) | 70 (Type J) / 200 (Type X) | 70 (Type J) / 200 (Type X) | ||||
Electrical class | PC | |||||||