Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AISIKAI MCCB Normal working conditions and installation methods |
|
Category | Requirements |
Elevation | Installation site not exceeding 2000 meters above sea level |
Ambient air temperature | The upper limit does not exceed+ 40 ºC; the lower limit does not exceed - 5 ºC; the average value of 24 hours does not exceed + 35 ºC |
Pollution Level | Level 3 |
Installation Category | Installation Category Ill, Circuit Breaker 1600A IV |
Atmospheric conditions |
Atmospheric relative humidity does not exceed 50% when the ambient air temperature is + 40 C. It can have a higher relative humidity at a lower temperature. The average maximum relative humidity of the wettest month is 90%, and the average minimum temperature of the month is + 25 C. Considering the condensation occurring on the surface of the product due to temperature changes. |
Installation Conditions |
Installed in places without significant shaking and shock vibration, the magnetic field near the installation site should not exceed 5 limes of the magnetic field in any direction, and leakage circuit breakers should generally be installed vertically. |
Installation | Circuit breaker can be installed vertically (i.e. vertically) or horizontally (i.e. horizontally). |
Input mode | Circuit breaker can't go down, that is, only 1,3,5 power lines, 2,4,6 load lines |
Technical performance specifications | |||||||
Model | ASKM1L-125 | ASKM1L-250 | ASKM1L-400 | ASKM1L-630 | |||
Frame rating current Inm(A) | 125 | 250 | 400 | 630 | |||
Rated current In(A) | 16,20,25,32,40,50,63,80,100,125 | 100,125,140,160,180,200,225,250 | 225,250,315,350,400 | 400,500,630 | |||
No.of poles | 3/4 | 3/4 | 3/4 | 3/4 | |||
Rated insulation voltage Ui(V) | AC800 | ||||||
Rated operational voltage Ue(V) | AC400 | AC400 | AC400 | AC400 | |||
Rated impulse withstand voltage Uimp(V) | 8000 | 8000 | 8000 | 8000 | |||
Arc distance(mm) | ≯50(0)** | ≯50(0)** | ≯100(0)** | ≯100(0)** | |||
Breaking capacity level | M | M | M | M | |||
UItimate short-circuit breaking capacity Icu(kA) | AC400V | 50 | 50 | 65 | 65 | ||
Service short-circuit breaking capacity Ics(kA) | AC400V | 35 | 35 | 50 | 50 | ||
Rated residua action current I△n(A) |
AC type residual current protection |
U type tripper,non-delay | 0.03/0.1/0.3/0.5 | 0.03/0.1/0.3/0.5 | - | - | |
V type tripper,switchable between non-delay and delay | 1.0/0.3/0.5 | 0.1/0.3/0.5 | 0.1/0.3/0.5 | 0.3/0.5/1 | |||
W type tripper,switchable between non-delay and delay | 0.3/1/3/10 | 0.3/1/3/10 | 1/3/10/30 | 1/3/10/30 | |||
A type residual current protection | VA type tripper,switchable between non-delay and delay | 0.1/0.3/0.5 | 0.1/0.3/0.5 | 0.1/0.3/0.5 | 0.3 /0.5/1 | ||
Use category | A A | ||||||
Rated residual non-action current I△no(mA) | ½ I△n(A) ½ I△n(A) | ||||||
Rated residual short-circuit making(breaking)capacity I△m(kA) | ¼Icu ¼ Icu | ||||||
Operational performance(times)* | Electrical service life(times) | 8000 | 8000 | 7500 | 7500 | ||
Mechanical service life(times)-without maintenance | 20000 | 20000 | 10000 | 10000 | |||
Mechanical service life(times)-with maintenance | 40000 | 40000 | 20000 | 20000 | |||
outine dimensions(mm) | W(3P/4P) | 92/122 | 107/142 | 150/198 | 210/280 | ||
L | 150 | 165 | 257 | 280 | |||
H | 92 | 90 | 106.5 | 115.5 |