Customization: | Available |
---|---|
Warranty: | 1 Year |
Brand: | Aisikai |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ASKQ6 Series Intelligent Automatic Transfer Switch |
Frame-80 | Frame-125 | Frame-250 | Frame-400 | Frame-630 | |||||
Frame rating current | 80 | 125 | 250 | 400 | 630 | |||||
Rated current (A) | 16,25,32,40,50,63,80 | 63,80,100,125 | 125,160,200,250 | 250,320,400 | 500,630 | |||||
Standards complied | GB/T14048.11-2016(IEC69047-6-1) | |||||||||
Rated current (Hz) | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||||
Number of poles(P) | 2 | 3,4 | 2 | 3,4 | 2 | 3,4 | 2 | 3,4 | 2 | 3,4 |
Rated working voltage Ue(V)AC | 230 | 400 | 230 | 400 | 230 | 400 | 230 | 400 | 230 | 400 |
Rated insulation voltage Ui(V)AC | 800 | 800 | 800 | 800 | 800 | |||||
Rated impulse withstand voltage Uimp(kV) | 8 | 8 | 8 | 8 | 8 | |||||
Rated limit short-circuit current lq(use fuse for protection)(kA) | 100 | 100 | 100 | 100 | 100 | |||||
Rated short time withstand current Icw (kA/s) | 5kA/60ms | 5kA/60ms | 10kA/60ms | 10kA/60ms | 17kA/60ms | |||||
Rated short-circuit making capacity Icm (kA) | 7.65 | 17 | 17 | 17 | 17 | |||||
Use category | AC-33A | AC-33A | AC-33A | AC-33A | AC-33A | |||||
Mechanical service life(times) | 10000 | 10000 | 10000 | 10000 | 10000 | |||||
Electric service life (times) | 6000 | 6000 | 6000 | 6000 | 6000 | |||||
Operation cycles (times/hour) | 120 | 120 | 120 | 120 | 120 | |||||
Making and breaking capacity (kA) | 0.63 | 1 | 2.5 | 4 | 5 | |||||
Making and breaking times (times) | 50 | 50 | 50 | 50 | 50 | |||||
Contact switching time (ms) | 70 | 70 | 70 | 70 | 70 | |||||
Electric level | Dedicated integrated PC level | |||||||||
One-piece weight (Kg) | 7.7 | 9.1 | 10.4 | 21.5 | 23.4 |
The automatic transfer switch is suitable for AC below 415V,rated frequency 50Hz,DC250V and below.All specifications are available in 3-pole and 4-pole.2-pole products are available below 400A.This product is mainly used for the primary load specified by the state,and is widely used in important areas of fire fighting,post and telecommunications,hospitals,hotels,high-rise buildings,industrial assembly lines,and TV stations that need continuous power supply.The main and backup power supply can be grid and grid,
automatic start generator set,battery set,etc.
STRUCTURE INTRODUCTION
NORMAL WORKING CONDITIONS AND INSTALLATION METHODS | |
ltems | Requirements |
Operating temperature |
-20 to 40ºC.The average value for 24 hours shall not exceed +35ºC |
Operating humidity |
The average humidity at+40°ºC shall not exceed 50%. Higher relative humidity is allowed at lower temperatures,for example,up to 90%at +25°ºC.Special measures should be taken for occasional condensation due to temperature changes |
Altitude | Lower than 2000 meters and,if higher than 2000 meters,please use at reduced ratings |
Vibration and gas |
There shall be no strong vibration or shock and no harmful gases to corrode the metals and to damage the insulation within the environment of its use |
Surrounding materia |
There shall be no serious dust,conductive particles or explosive hazardous substances |
Class of pollution |
Class 3 according to GB/T14048.11 |
Class of installation |
Class IV according to GB/T14048.11 |
Installation inclination |
The product is fixedly installed in the cabinet,the maximum inclination is+22.5 |
Arcing distance inclination |
AC 380V,arcing distance is 80mm;flashover 660V,arcing distance is 100mm. |