AISIKAI MCCB Normal working conditions and installation methods |
|
Category | Requirements |
Elevation | Installation site not exceeding 2000 meters above sea level |
Ambient air temperature | The upper limit does not exceed+ 40 ºC; the lower limit does not exceed - 5 ºC; the average value of 24 hours does not exceed + 35 ºC |
Pollution Level | Level 3 |
Installation Category | Installation Category III, Circuit Breaker 1600A IV |
Atmospheric conditions |
Atmospheric relative humidity does not exceed 50% when the ambient air temperature is + 40 C. It can have a higher relative humidity at a lower temperature. The average maximum relative humidity of the wettest month is 90%, and the average minimum temperature of the month is + 25 C. Considering the condensation occurring on the surface of the product due to temperature changes. |
Installation Conditions |
Installed in places without significant shaking and shock vibration, the magnetic field near the installation site should not exceed 5 limes of the magnetic field in any direction, and leakage circuit breakers should generally be installed vertically. |
Installation | Circuit breaker can be installed vertically (i.e. vertically) or horizontally (i.e. horizontally). |
Input mode | Circuit breaker can't go down, that is, only 1,3,5 power lines, 2,4,6 load lines |
MCCB have 3-section protection function(LSI,i.e.overload long delay protection+short-circuitshort delay protection+grounding protection ),4-section protection function(LSIG,i,e.overload long delay protection
+short-circuit short delay protection+short-circuit instantaneous
protection+grounding protection)and under-voltage protection function.
MCCB can protect circuits and power equipment from damage.Low temperature to -40 ºC type circuit breaker is available.
MCCB can distribute power and protect circuits and power equipment against faults like overload,under-voltage,short-circuit and under-voltage.The products have the characteristics of small volume,high breaking capacity,short flying arc,vibration resistant,etc.The whole
series have isolation function.
Model | ASKM1E-400 | ASKM1E-630 | ASKM1E-800 | ||||||
Frame rating current Inm(A) | 400 | 630 | 800 | ||||||
Rated current In(A) | 400 | 630 | 800 | ||||||
Overload long delay setting current Ir(A) |
200,225,250,280, 315,350,400 |
400,420,440,460,480, 500,530,560,600,630 |
630,640,660,680,700, 720,740,760,780,800, |
||||||
Rated operational voltage Ue(V) | AC400V/415V AC660V/690V | ||||||||
Rated insulation voltage Ui(V) | 1000V | ||||||||
Rated impulse withstand voltage Uimp(V) | 12000V | ||||||||
Arc distance(mm) | ≯100(0)2) | ≯100(0)2) | ≯100(0)2) | ||||||
Breaking capacity level | M | H | M | H | M | H | |||
Ultimate short-circuit breaking capacity Icu(kA) |
AC400V/415V | 65 | 100 | 65 | 100 | 65 | 100 | ||
AC660V/690V | 20 | 20 | 20 | 20 | 20 | 20 | |||
Service short-circuit breaking capacity Ics(kA) |
AC400V/415V | 50 | 65 | 50 | 75 | 50 | 75 | ||
AC660V/690V | 15 | 15 | 15 | 15 | 15 | 15 | |||
Rated short-time withstand current lcw(kA)/1s | 8 | 10 | 10 | ||||||
Use category | B | B | B | ||||||
Eectrical service life(times) |
7500 | 7500 | 7500 | ||||||
Mechanical service life(times) |
without maintenance | 10000 | 10000 | 10000 | |||||
with maintenance | 20000 | 20000 | 20000 | ||||||
Outine dimensions (mm) |
W(3P/4P) | 150/198 | 210/280 | 210/280 | |||||
L | 257 | 280 | 280 | ||||||
H(not including handle) | 106.5 | 115.5 | 115.5 |