AISIKAI MCCB Normal working conditions and installation methods |
|
Category | Requirements |
Elevation | Installation site not exceeding 2000 meters above sea level |
Ambient air temperature | The upper limit does not exceed+ 40 ºC; the lower limit does not exceed - 5 ºC; the average value of 24 hours does not exceed + 35 ºC |
Pollution Level | Level 3 |
Installation Category | Installation Category Ill, Circuit Breaker 1600A IV |
Atmospheric conditions |
Atmospheric relative humidity does not exceed 50% when the ambient air temperature is + 40 C. It can have a higher relative humidity at a lower temperature. The average maximum relative humidity of the wettest month is 90%, and the average minimum temperature of the month is + 25 C. Considering the condensation occurring on the surface of the product due to temperature changes. |
Installation Conditions |
Installed in places without significant shaking and shock vibration, the magnetic field near the installation site should not exceed 5 limes of the magnetic field in any direction, and leakage circuit breakers should generally be installed vertically. |
Installation | Circuit breaker can be installed vertically (i.e. vertically) or horizontally (i.e. horizontally). |
Input mode | Circuit breaker can't go down, that is, only 1,3,5 power lines, 2,4,6 load lines |
Technical performance specifications | ||||||||||||
Model | ASKM1-630 | ASKM1-800 | ASKM1-1600 | |||||||||
Frame rating current Inm(A | 630 | 800 | 1600 | |||||||||
No.of poles | 3P/4P | 3P/4P | 3P/4P | |||||||||
Rated current In(A) | 400,500,630 | 400,500,630,700,800 | 800,1000,1250,1600 | |||||||||
Rated insulation voltage Ui(V) | 1000V | 1000V | 1000V | |||||||||
Rated impulse withstand voltage Uimp(V | 12000V | 12000V | 12000V | |||||||||
Rated operational voltage Ue(V) | AC400V/415V AC660V/690V | |||||||||||
Arc distance(mm) | +100(0)2 | +100(0)2) | +100(0)2 | |||||||||
Breaking capacity level | L | M | H | L | M | H | L | M | H | |||
UItimate short-circuit breaking capacity Icu(kA) |
AC400V | 70 | 75 | 100 | 75 | 85 | 100 | 85 | 85 | 85 | ||
20 | 30 | 30 | 20 | |||||||||
Service short-circuit breaking capacity lcs(kA) |
AC400V | 70 | 75 | 100 | 75 | 75 | 85 | 65 | 65 | 65 | ||
20 | 30 | 30 | 20 | |||||||||
Use category | A | A | A | |||||||||
Electrical service ife(times) |
AC400V/415V | 7500 | 7500 | 7500 | ||||||||
AC660V/690V | 1000 | 500 | 1000 | |||||||||
Mechanical service ife(times) |
without maintenance | 10000 | 10000 | 20000 | ||||||||
with maintenance | 20000 | 20000 | 20000 | |||||||||
Outine dimensions(mm) |
W(3P/4P) | 182/240 | 210/280 | 210/280 | ||||||||
L | 270 | 280 | 470 | |||||||||
H(not induding handle) | 110 | 115.5 | 154 |